AUX SETTING FOR MODEL BB - EB (SET)
Aux 01 Change of alarm relay contact
Setup:

0 = Relay K2 Open with alarm and with autoreset
1 = Relay K2 Open with alarm and with memory
2 = Relay K2 Closed with alarm and with autoreset
3 = Relay K2 Closed with alarm and with memory
Aux 02 Electric control for solenoid valve
Setup:

0 = Electric control for solenoid valve excluded
1 = Electric control for solenoid valve active
Aux 03 Threshold setup B8a
B8a = Short-circuit protection of every single output

Threshold setup B8a (E = Automatic)

The value to be set depends on the type of solenoid valves and on the output voltage. For more information contact our technical office.
Aux 04 Stop cycle for low dP
If dP control is active (Set F07 = 1), the cleaning cycle starts and stops according to the dP reading.
With dP reading under the STOP threshold the cleaning cycle stops and the display shows dP reading and letter P alternatively. The cleaning cycle stop is at the end of the cycle.
With dP reading over the START threshold the cleaning cycle is able to start.

Setup:

0 = Pause low dP: Stop at the end of cycle
1 = Pause low dP: instantaneous Stop