ESA Electronic Engineering
AUX SETTING FOR MODEL SC - LC - LSB (SET)
Aux 02 Select dP range
Setup:

10 = Select range 10 kPa
7 = Select range 7 kPa
5 = Select range 5 kPa
3 = Select range 3 kPa
1 = Select range 1 kPa
Aux 03 Change alarm relay output contact
Setup:

0 = Relay Open with alarm and with autoreset
1 = Relay open with alarm and with memory
2 = Relay Closed with alarm and with autoreset
3 = Relay Closed with alarm and with memory
Aux 04 Cycle stops for low dP
Setup:

C1a = Pause low dP: Stop at the end of cycle

The cleaning STOP threshold: if dP is below this threshold, the cleaning cycle stops and the display shows 'CYCLE STOP FOR LOW dP' or the letter 'P' according to the model. The cleaning cycle stops at the end of the cycle (Set 13).

C1c = Pause low dP: instantaneous Stop

Set the cleaning STOP threshold: if dP is below this threshold, the cleaning cycle stops and the display shows 'CYCLE STOP FOR LOW dP' or the letter 'P' according to the model. The cleaning cycle stops immediately and as soon as the start threshold is reached. The cycle will restart from the point of stop (Set 13).
Aux 05 Additional cycles management by dP reading or contact
Setup:

0 = Additional cycles management by dP reading
1 = Additional cycles management by closed contact on 3rd Input (Terminal 16-17)
2 = Additional cycles management by contact instead of D5 (Terminal 12-13)
Aux 06 Additional post-cleaning cycles
Setup:

0 = Additional cycles with enable at STOP
1 = Additional cycles with enable at START
2 = Additional cycles ALWAYS enabled
Aux 08 Electric control on solenoid valve
Setup:

0 = B8 - B9 excluded
1 = B8 active - B9 excluded
2 = B8 excluded - B9 active
3 = B8 - B9 active

B8=In case of short circuit, the output is automatically skipped
B9=If a solenoid valve is not activated, the relay indicate the alarm condition
Aux 09 Short circuit threshold setup
Shortcircuit threshold setup (000 = Automatic)

The value to be set depends on the type of solenoid valves and the output voltage. For more information contact our technical office.
Aux 10 Control relay K1
Setup:

A2 = Voltage presence on relay K1
A3 = Relay cycle On/Off on relay K1
Aux 11 Keypad lock
Setup:

0 = Keypad lock off
1 = Keypad lock on

To avoid unintentionally changing of the set up parameters of the device, it is possible to lock the keyboard. If the keyboard is locked, the display will shows LOCK (and MAN or AUTO alternatively in case of sequencer with digital dP control) or E10 depending on the sequencer model.
In SB and DB model the Led Ld22 is On with keybaord lock. To release the keyboard, contact the supplier.