AUX SETTING FOR MODEL PC (SET)
Aux 02 Compressed air control by contact
Setup:

0 = Excluded
1 = Included (input 3, clamps 16-17)
Aux 03 Change of output alarm relay contacts
Setup:

0 = Relay K2 open with alarm and with autoreset
1 = Relay K2 open with alarm and with memory
2 = Relay K2 closed with alarm and with autoreset
3 = Relay K2 closed with alarm and with memory
Aux 04 Cycle stops for low dP
Setup:

C1a = Pause for low dP: Stop at the end of cycle
C1c = Pause for low dP: instantaneous Stop
Aux 08 Electric control on solenoid valve
Setup:

0 = B8 - B9 excluded
1 = B8 active - B9 excluded
2 = B8 excluded - B9 active
3 = B8 - B9 active

B8 = Short-circuit protection of every single output
B9 = Electric control of output activation
Aux 09 Threshold setup B8b
Threshold setup B8b (000 = Automatic)
B8b = Short-circuit protection of every single output against short circuit.
The value to be set depends on the type of solenoid valves and on the output voltage. For more information contact our technical office.
Aux 10 Control relay K1
Setup:

A2a = Voltage presence on Relay K1
If the device is supplied, relay K1 is activated and the terminal board contact is closed. In case of power failure, this contact is open.

A3a = Relay cycle On/Off on Relay K1
If the cleaning cycle is active, the contact of relay K1 on the terminal board is closed. If cleaning cycle stops for any reason, contact K1 opens.