SETTING FOR MODEL BPB (SETUP)
Set 01 Zero dP readout regulation
In this set up code, it is possible to adjust the zero reading of differential pressure.
In this function the display shows the dP reading and, when the plant stops or air pipes are not connected, if the dP reading is not 0.00 kPa it is possible to adjust it by key A and C.
Set 02 Minimum dP alarm threshold
Setup:

E = Min dP alarm excluded
x.xx = min dP alarm threshold value

If set to 'OFF' or 'E' (according to the model), the function is excluded. NOTE: the minimum dP alarm is delayed by 60 seconds by default after the activation of the first cleaning cycle.
Set 03 Maximum dP alarm threshold.
The activation of this alarm is delayed by 20 seconds by default.