SETTING FOR MODEL DPC (SETUP)
Set 00 Multilanguage display
In Set up it is possible to select the language of all the descriptions showed by the display:

Italian
English
French
German
Spanish
Set 01 Zero dP readout regulation
In this set up code it is possible to adjust the zero reading of differential pressure.
In this function the display shows the dP reading and, when the plant stops or air pipes are not connected, if the dP reading is not 0.00 kPa, it is possible to adjust it by key A and C.
Set 02 Minimum dP alarm
If the dP readout is below the threshold in Set up, the minimum dP alarm is activated.
The display shows the alarm condition code E8 (see the alarm description) or the dP readout and letter L alternatively, according to the model.
The corresponding alarm relay will signal its condition.
The alarm is automatically reset when the dP readout is above the threshold again.
With set to 'OFF' or 'E' (according to the model), the function is excluded.
NOTE: the minimum dP alarm is delayed by 60 seconds by default after the activation of the first cleaning cycle.
Set 03 Maximum dP alarm
If the dP readout is above the threshold in Set up, the maximum dP alarm is activated.
The display shows the alarm condition code E7 (see the alarm description) or the dP readout and letter H alternatively, according to the model.
The corresponding alarm relay will signal its condition.
The alarm is automatically reset when the dP readout is below the alarm threshold again.
The activation of this alarm is delayed by 20 seconds by default.
Set 04 Operating hour-counter
In Set up it is possible to visualize an hours counter.
This counter is always active in operating and it stops in Set up.